Product CenterPRODUCTS
<
>

Combined low dew point compressed air dryer

working principleThe combined low dew point dryer is composed of a freezing dryer and an adsorption dryer (heatless or heated) through reasonable pipeline connection and volume matching. The freezing
  • Product features
  • Product specification
  • Accessories
working principle
The combined low dew point dryer is composed of a freezing dryer and an adsorption dryer (heatless or heated) through reasonable pipeline connection and volume matching. The freezing dryer has very strong water removal capacity, low operating energy consumption, and no air loss. It combines with the adsorption dryer to achieve a low dew point, giving full play to their advantages. Before the compressed air enters the adsorption dryer, the freezing dryer is used for pre-treatment, so that a large amount of water is removed in the freezing dryer first, and then enters the adsorption dryer for deep drying, which can achieve a very low pressure dew point, up to - 70 ℃. It makes use of the strong water removal capacity of the freezing dryer to greatly reduce the water inlet load of the drying tower. The water entering the adsorption tower after cold drying treatment is about 20% of that of the ordinary dryer. Under other conditions, the low dew point dry air used to absorb water vapor can also be reduced by the same extent. That is, the amount of regeneration gas is about 1/5 of that of ordinary adsorption dryers, which really creates conditions for reducing regeneration energy consumption, especially for saving regeneration gas energy consumption. Thus, the economic operation point and low dew point product gas are achieved.

Operating conditions and technical indicators
Inlet pressure: 0.6~1.0Mpa
Outlet air pressure dew point: - 40~- 70 ℃
Pressure drop: ≤ 0.05Mpa
Cooling water temperature: ≤ 32 ℃
Inlet temperature: ≤ 45 ℃
Purge air: 3~5 ℃
Air cooling/water cooling (optional)

model

Air handling capacity

Air connecting pipe diameter

Compressor power

Circulating volume of cooling water

Power Supply

Net weight of equipment KG

Overall dimensions  Companymm

long

wide

high

DM15ZH

1.5

ZG1’’

0.65

 

 

Air-cooled

 

220/50

or

380/50

295

980

750

1453

DM26ZH

2.6

ZG1’’

0.75

350

980

800

1653

DM40ZH

3.8

ZG1½’’

1.25

485

1200

1000

1535

DM65ZH

6.5

DN50

1.5

655

1200

1000

1994

DM110ZH

11

DN65

3

750

1460

1180

2065

DM150ZH

17

DN80

4

3

 

 

 

 

 

380/50

950

1680

1180

2140

DM200ZH

23

DN80

5

3.5

1220

1750

1800

2150

DM300ZH

33

DN100

7.5

6

1460

1650

2000

2480

DM400ZH

45

DN125

10.5

7.4

1980

1980

2580

2717

DM500ZH

55

DN125

12.5

8

2500

2520

1900

2750

DM600ZH

65

DN125

15

10

2950

2550

1900

2780

DM800ZH

85

DN125

20

12

3550

2650

2600

2920

DM1000ZH

110

DN150

25

14

4200

2690

2600

2960

DM1200ZH

130

DN150

25

16

4500

3000

2950

3000

DM1500ZH

150

DN200

40

18

7690

3200

2950

3000

DM2000ZH

200

DN200

50

24.4

8900

3200

3000

3000

 


Online consultation Online consulting